Description

MODEL

TEMP

WATTS

VOLTS

CABLE TYPE

CABLE INSULATION TYPE

LTD 140 °F/ 60 °C 10 240 DOMESTIC HOT BRAIDED OVER JACKET

Features:

The standard product offering has been designed to maintain nominal domestic water temperatures of +105 °F, +115 °F, +125 °F, and +140 °F. These representative hot water temperatures are in accordance with the ASHRAE Applications Handbook.

The heating cables are UL Listed for domestic hot water temperature maintenance and meet all requirements of IEEE Standard 515.1, Recommended Practice for the Testing, Design, Installation, and Maintenance of Electrical Resistance Heat Tracing for Commercial use.

Nelson Type LT self-regulating heater cable is a parallel circuit electric heater strip. Irradiation cross-linked conductive polymer core material is extruded over the multi-stranded, tin-plated, 16 gauge copper bus wires.

The conductive core material increases or decreases its heat output in response to temperature changes. Two jackets
provide extra dielectric strength, moisture resistance, and protection from impact and abrasion damage.

The inner thermoplastic jacket is extruded over and bonded to the core material. A thermoplastic elastomer outer jacket is then extruded over the inner jacket. A stranded tinned copper metal braid is supplied on all heaters. A color-coded modified polyolefin over jacket is provided for identification during installation.

Type LT-D Domestic Hot Water Cable Specification/Application Information